Sep 18, 2026
4 demerits
· 1 violation
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level doors shall be self-closing, self-latching or self-closing and child protected by audible alarm. Observed door that leads from locker room area to pool deck not self-latching or audibly alarmed. Correct within 30 days. ITS issued.
View this inspection on the county portal ›
Feb 24, 2026
6 demerits
· 1 violation
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Observed pool side emergency phone to be unable to transmit voice communication at the time of inspection. Aquatic director’s office phone was made available as a temporary emergency phone. This phone is a VOIP phone and 911 calls from it do not go directly to local 911, but instead to the national 911 call center in Colorado where they could be routed. The pool side emergency phone must be corrected, the temporary use of the office phone cannot be a permanent correction. The office must remain open and accessible for the duration of the temporary use when the pool is open so that the phone can be accessed. Signs with the address, phone number, and dialing instructions were placed, as was a sign indicating where the temporary 911 phone is located. C. Elmore will follow-up on the phone on Monday 3/2/2026. Failure to correct the pool side emergency phone may result in closure of the pool until it is corrected.
View this inspection on the county portal ›
Nov 18, 2025
8 demerits
· 3 violations
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
.2535(6) Automatic chlorine and bromine feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation. Observed control board not to demonstrate automatic shut off when flow stops. The control board must demonstrate automatic shut off while still powered but with no flow. Intent to Suspend issued. Deadline is 12/18/2025.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed pipe leaks in the pump room. Correct the leaks.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(i) Water in restrooms shall not exceed 110 F. Measured the water temperature to be 115F at the sink.
View this inspection on the county portal ›
Apr 3, 2025
0 demerits
· 0 violations
No violations were recorded for this inspection.
View this inspection on the county portal ›
Nov 14, 2024
8 demerits
· 2 violations
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(a) Provide depth markers on pool walls and pool deck next to the swimming pool. Observed one depth marker missing at the 10ft. Depth. Resulting in 42ft. Distance between markers. Markers shall be on the wall as it is a gutter pool. New depth marker was placed. -CDI
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed doors to be propped open. Door cannot be propped open as this defeats the requirement that they be self-closing and self-latching. Keep the doors properly self-closing and self-latching. Unattended doors had their props removed. -CDI
View this inspection on the county portal ›
Feb 1, 2024
0 demerits
· 0 violations
No violations were recorded for this inspection.
View this inspection on the county portal ›
Oct 13, 2023
8 demerits
· 2 violations
#13 · Pool maintenance: contrasting band on steps and benches −4
.2532(13) Contrasting color bands shall be used on the leading edge of step treads, seats, and benches.
.2521(b) Provide at least 2" contrasting color band to edge of stair treads.
Observed some stair treads to have the contrasting bands worn away. Correct the contrasting bands. Intent to Suspend issued. 11/13/2023 is the deadline.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed 1 locker room door to not be self-closing/self-latching. Correct the door. Intent to Suspend issued. Deadline is 11/13/2023.
View this inspection on the county portal ›
Mar 29, 2023
8 demerits
· 2 violations
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed 1 missing eyeball return fitting. Replace the fitting. No Permit Action taken.
#13 · Pool maintenance: contrasting band on steps and benches −4
.2521(b) Provide at least 2" contrasting color band to edge of stair treads.
.2521(b) Provide at least 2"x 2" tile for contrasting color band within 1" of adjacent tiles and edge of the stair tread.
Observed contrasting strip on plastic stairs to be fading. Correct this before it becomes too faded to contrast clearly with the stair edge. No Permit Action taken.
View this inspection on the county portal ›
Nov 16, 2022
6 demerits
· 1 violation
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530 - Body Hook attached to pole with cleaning brush attached to other end which could impede use. CDI - lifeguard removed brush.
View this inspection on the county portal ›
Jan 27, 2022
0 demerits
· 0 violations
No violations were recorded for this inspection.
View this inspection on the county portal ›
Oct 27, 2021
2 demerits
· 1 violation
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed storage of non pool items in pump room. Eliminate storage of non pool items in pump room.
View this inspection on the county portal ›
Mar 22, 2021
0 demerits
· 0 violations
No violations were recorded for this inspection.
View this inspection on the county portal ›
Dec 21, 2020
2 demerits
· 1 violation
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed some debris in pump room. keep pump room free of debris.
View this inspection on the county portal ›
Jan 13, 2020
6 demerits
· 2 violations
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter appears to be stuck. Repair.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed trash and other non pool items in pump room. Eliminate storage of non pool items in pump room.
View this inspection on the county portal ›
Sep 10, 2019
26 demerits
· 7 violations
#3 · Water quality: pool water pH −6
Pool pH at 7.0. Required at 7.2 to 7.8. Corrected to 7.2 during inspection.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Alkalinity not recorded weekly. Record weekly. Intent to Suspend issued.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One door not self-closing, self-latching. Getting stuck when opened. Located near locker room entry. Repair to self-close, self-latch. Intent to Suspend issued.
#18 · Premises: lifeguards present or warning signs posted −4
Some standing water on pool deck next to pool coping. Did not notice any build-up below water. Continue to monitor and keep deck free of standing water.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operational. Repair to operational. Intent to Suspend issued.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Floor in pump room/chemical storage room wet due to backwash of pump. Open pipe on side of backwash pit that allows overflow of water on to pump room floor which drains to chemical storage room. Keep pump room floor dry.
#31 · Dressing and sanitary facilities: sewage disposed of in a properly operating sewage system −2
Backwash water goes directly to drain without air gap. Install air gap or approved backflow prevention/check valve.
Water line check valve does not meet .2512. If ever replaced, replace with approved check valve. Original construction.
View this inspection on the county portal ›
Mar 4, 2019
8 demerits
· 2 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Throw rope for ring buoy was 50' long. It should be kept at 45' which is 1.5 times the width of pool. Corrected during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Equipment is in basement and there appears to be a small leak coming through wall when it rains. Observed water on floor. Keep equipment and chemical area dry. Leak was adjacent to chemical storage room in pump room.
View this inspection on the county portal ›
Dec 3, 2018
14 demerits
· 4 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed main drain checks not being recorded. Record daily main drain checks. Intent to Suspend issued.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Portable steps with slip-resistant tread beginning to wear. Maintain as slip-resistant. Area with wear not large enough to present a slip hazard. Continue to monitor and repair as needed.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door into locker room left propped open. Door sticks to magnetic prop. Door shall self-close, self-latch at all times. Intent to Suspend issued. Repeat violation.
.2537(b) All gates and doors shall be self-closing, self-latching.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Observed pool drain routed directly to backwash pit with no backflow prevention/air gap. Provide check valve to eliminate cross contamination.
Pool being filled by hose. Hose was left in the pool. Provide an air gap.
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer.
View this inspection on the county portal ›
Feb 7, 2018
12 demerits
· details not yet loaded
Violation details for this inspection are not yet loaded on this site. We're still importing older records — check the official county portal for the full report.
Oct 10, 2017
24 demerits
· details not yet loaded
Violation details for this inspection are not yet loaded on this site. We're still importing older records — check the official county portal for the full report.
May 23, 2017
6 demerits
· details not yet loaded
Violation details for this inspection are not yet loaded on this site. We're still importing older records — check the official county portal for the full report.
Dec 6, 2016
6 demerits
· details not yet loaded
Violation details for this inspection are not yet loaded on this site. We're still importing older records — check the official county portal for the full report.
Feb 3, 2016
16 demerits
· details not yet loaded
Violation details for this inspection are not yet loaded on this site. We're still importing older records — check the official county portal for the full report.
Oct 28, 2015
6 demerits
· details not yet loaded
Violation details for this inspection are not yet loaded on this site. We're still importing older records — check the official county portal for the full report.
Apr 7, 2015
6 demerits
· details not yet loaded
Violation details for this inspection are not yet loaded on this site. We're still importing older records — check the official county portal for the full report.
Oct 20, 2014
10 demerits
· details not yet loaded
Violation details for this inspection are not yet loaded on this site. We're still importing older records — check the official county portal for the full report.
Feb 5, 2014
2 demerits
· details not yet loaded
Violation details for this inspection are not yet loaded on this site. We're still importing older records — check the official county portal for the full report.
Oct 10, 2013
4 demerits
· details not yet loaded
Violation details for this inspection are not yet loaded on this site. We're still importing older records — check the official county portal for the full report.