Oct 19, 2026
22 demerits
· 5 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Cyanuric acid checks are not required if cyanuric acid (stabilizer) is not used.
Observed the log record to be missing entries for a significant number of days. Keep the records properly. The certified pool operator must attend the pool every day the pool is open. The checks must be made and recorded for every day the pool is open.
#13 · Pool maintenance: contrasting band on steps and benches −4
.2521(b) Provide at least 2" painted contrasting color band to edge of stair treads.
Or
.2521(b) Provide at least 2"x 2" tile for contrasting color band within 1" of adjacent tiles and edge of the stair tread.
Observed the contrasting color bands of the stairs to be stripped off. They must be replaced with correct contrasting bands.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed the rear pool door leading to the outside to be off the hinge and not opening/closing properly. Correct the door and ensure that it is fully self-closing and fully self-latching.
#22 · Premises: emergency telephone provided −6
.2530(f) Pool telephone shall be capable of directly dialing 911 or another emergency notification system.
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.
.2530(f) Emergency phone shall remain operable.
Observed the emergency phone to auto-dial the front desk of the hotel, rather than 911 or allow dialing of 911. Observed the posted phone number to not be in service. The phone must be able to dial out to local 911 and also be able to receive calls at the posted telephone number.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep the flow meter operational. Observed the flow meter to not be operational.
View this inspection on the county portal ›
Nov 18, 2025
38 demerits
· 11 violations
#2 · Water quality: disinfectant residual provided by −6
No free chlorine in the pool. .2535(4) Maintain chlorine at least 1.0 ppm. - Corrected to 3ppm.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No recent total alkalinity, cyanuric acid, or maintenance activities. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Intent to suspend item.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Pile of debris in the deep end of the pool. .2537(14) Keep pool surface and pool floor free of debris. - Intent to suspend item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrail loose. .2521 Install handrails per manufacturer instructions.
Both ladders loose. .2521 Install ladders per manufacturer instructions.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Chairs around handrail and in front of back door. .2522(e) Provide at least 5 ft of clear walking space around diving board, handrail, slide, or other permanent structure on a swimming pool deck. - Intent to suspend item.
#22 · Premises: emergency telephone provided −6
Emergency phone not functioning. .2530(f) Emergency phone shall remain operable and shall be capable of directly dialing 911 or another emergency notification system. - Corrected.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Vacuum off in the pump room. Observed vacuum cap not closed, spring damaged. .2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. - Intent to suspend item.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Difficult to access equipment due to low ceiling height. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Leak in the pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Some piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restroom 224F. .2526(i) Water in restrooms shall not exceed 110 F.
View this inspection on the county portal ›
Apr 14, 2025
24 demerits
· 6 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No recent temperature, total alkalinity, or main drains checks. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Pre-permit item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder loose. .2521 Install ladders per manufacturer instructions. - Corrected.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed two new ring buoys and throw ropes. Ropes too long. .2530(a) Provide USCG approved ring buoy with attached 24 foot throw rope at least 1/4” inches diameter. - Corrected.
#22 · Premises: emergency telephone provided −6
Incorrect dialing instructions and pool phone number posted. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. - Corrected.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Vacuum cap not closed. .2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. - Corrected.
Spare pump basket not provided. .2518(e) Provide a spare basket for pump. - Pre-permit item.
Flow meter not functioning. .2518(g) Keep flow meter operational. - Pre-permit item.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restroom 126.6 F. .2526(i) Water in restrooms shall not exceed 110 F.
View this inspection on the county portal ›
Sep 25, 2023
28 demerits
· 7 violations
#2 · Water quality: disinfectant residual provided by −6
0.4ppm free chlorine. .2535(4) Maintain chlorine at least 1.0 ppm. - Pre-permit item.
#3 · Water quality: pool water pH −6
PH 6.9. .2535(1) Maintain pH at 7.2 to 7.8. - Pre-permit item.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Both skimmer baskets cracked. .2518(k) Replace missing or damaged skimmer basket. - Operator able to replace one of the baskets. - Pre-permit item.
#22 · Premises: emergency telephone provided −6
Incorrect dialing instructions posted. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. - Pre-permit item.
911 did not have any information for the phone. .2530(f) Emergency must remain operable, and be able to electronically transfer Automatic Number and Locator Identification for the phone. - Pre-permit item.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Shower sign not posted. .2526(a) Post a shower sign visible upon entrance to the pool.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restroom 113F. .2526(i) Water in restrooms shall not exceed 110 F.
View this inspection on the county portal ›
Jan 9, 2023
24 demerits
· 7 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No recent temperature, total alkalinity, or cyanuric acid checks. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Intent to suspend item.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck tile cracked and loose as you enter the ladder. .2537(2) Decks shall be structurally sound and kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. - Intent to suspend item.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Does not appear that there’s any ventilation in the pool room. Water dripping from the cieling. .2524(f) Indoor pools shall have mechanical ventilation.
#22 · Premises: emergency telephone provided −6
Phones down for the hotel this week while they upgrade their system. .2530(f) Emergency phone shall remain operable and shall be capable of directly dialing 911 or another emergency notification system. - Immediate suspension item.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Shower sign not posted. .2526(a) Post a shower sign visible upon entrance to the pool.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restroom > 110F. .2526(i) Water in restrooms shall not exceed 110 F.
View this inspection on the county portal ›
Oct 6, 2022
16 demerits
· 6 violations
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Pool room very humid. Not able to determine if there is any air movement. .2524(f) Indoor pools shall have mechanical ventilation.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter missing bobber. .2518(g) Install flow meter on return line per manufacturer instructions. - Corrected. Operator installed a different flow meter.
New flow meter installed only reads up to 70 GPM. Flow meter reads 64 GPM. .2518(g) Flow meter be capable of measuring 1.5 times the design flow rate. - Will follow up to ensure that facility has a flow meter that meets requirements.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Difficult to access equipment due to low ceiling height and other items. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Shower sign not posted. .2526(a) Post a shower sign visible upon entrance to the pool.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restroom 117.5F .2526(i) Water in restrooms shall not exceed 110 F.
View this inspection on the county portal ›