Oct 13, 2026
14 demerits
· 3 violations
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
.2539(d) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Documentation shall include an accurate Pool Drain Suction Compliance Form. Observed different pump in field than what is listed on pool drain suction compliance (PDSC) form. Permit suspended.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed depth markers near sun shelf and catwalk area not secured to pool deck. Resecure.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed gate near fitness area not self-latching. Repair.
View this inspection on the county portal ›
Apr 21, 2026
8 demerits
· 2 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed 1 weir missing out of 6 total. No Permit Action. More than 50% of weirs in place.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed gate on the front right side to not be self-latching. Door was corrected to be fully self-closing and fully self-latching. -CDI
View this inspection on the county portal ›
Apr 14, 2025
14 demerits
· 3 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
pH, chlorine, and main drains must be checked once a day and recorded every day the pool is open. Total Alkalinity and Cyanuric Acid (if Cyanuric Acid is in use) must be checked once a week, 100ppm maximum for Cyanuric Acid. Observed gaps in the log book record. Keep proper records for all daily and weekly requirements.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed 1 weir missing out of 6 total. No Permit Action. More than 50% of weirs in place.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Observed ring buoy throw rope to be 60 feet long. 50 foot length is required for this pool. Rope was corrected to the proper 50 foot length.
View this inspection on the county portal ›
Aug 16, 2023
28 demerits
· 6 violations
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm. Observed 0.0ppm-0.1ppm chlorine in the pool. Chlorination by the erosion feeder is required. Chlorine must be introduced by the chlorination system for normal operation and swimming. -I.S. Issued.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
pH, chlorine, and main drains must be checked once a day and recorded every day the pool is open. Total Alkalinity and Cyanuric Acid (if Cyanuric Acid is in use) must be checked once a week, 100ppm maximum for Cyanuric Acid. Observed many gaps in the log book record. Keep proper records for all daily and weekly requirements.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed 2 weirs missing out of 6 total. No Permit Action. More than 50% of weirs in place.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed vacuum line cap to be self-closing, but not self latching. It must close and latch such that a tool is required to open it.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length.
Observed throw rope to be dry rotted and to tear apart when tensioned. Replace the rope and make it exactly 50 foot length from end to attachment point on ring buoy. I.S. Issued.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed gate on the upper level at the front left side to be not self-closing and self-latching. Door must be corrected to be fully self-closing and fully self-latching.
View this inspection on the county portal ›