PARKVIEW APARTMENTS

350 COMMERCE CENTRE DR, Huntersville, NC 28078
Year-Round Swimming Pool · NC permit/State ID 2060530843
Latest result16 demerits
Last inspectedSep 9, 2026
Inspections on record3
On record sinceApr 17, 2026

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

01938 Apr 17, 2026: 38May 18, 2026: 8Sep 9, 2026: 16
Apr 17, 2026Lower is betterSep 9, 2026

Inspections & violations

Sep 9, 2026 16 demerits · 4 violations
Inspector comments: POOL IS NOT APPROVED FOR NIGHT SWIMMING. THE POOL CANNOT BE OPEN FOR SWIMMING AFTER SUNSET OR BEFORE SUNRISE. CHANGE THE SIGNS TO REFLECT THIS, FOR EXAMPLE THEY COULD READ “POOL OPEN FOR SWIMMING FROM DAWN TO DUSK” OR “POOL OPEN FOR SWIMMING FROM SUNRISE TO SUNSET”. MAIN DRAIN COVERS EXPIRE 3/12/2031 Permit restriction: Pressure and vacuum gauges must remain in place and operational gate valve must remain locked in place. TDH must be between 63 and 82 ft. head loss or 78 GPM to 106 GPM for minimum turnover and restriction of the filter. TDH less than 53 or 119 GPM exceeds the main drains. SUCTION HAZARD. DO NOT LEAVE LADDERS OR OTHER ITEMS WHERE THEY CAN PROVIDE A FOOT-HOLD FOR CLIMBING OVER THE POOL FENCE.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Pool has permit restriction for the circulation system where vacuum gauge and pressure gauge must be properly installed so that TDH can be measured. Also, valve handle was found in a new position relative to the previous position it should be in. This new position appears to open up the valve more. Return the valve to the previous position. The vacuum gauge must be replaced and the valve handle returned to the previous position and secured there with the padlock. Immediate Suspension issued. Contact C. Elmore (704-507-6814) when the correction is made. Pool is closed to swimming by order of the Health Department until the correction is verified.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed typographical error in the phone number. Corrected to 205-983-3411.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms > 110 F. .2526(i) Water in restrooms shall not exceed 110 F.

View this inspection on the county portal ›

May 18, 2026 8 demerits · 4 violations
Inspector comments: Inspection conducted with CPO Jaxon Goldenberg-Sheetz and Johnny Hoffiz. TDH for pump is (0.5x1.13) + (25.5x2.31) = 59.5 or 111 GPM per pump curve. Main drains only capable of handling 119 GPM. TR-140 filter only capable of handling 106 GPM. Since pool was built, facility replaced the filter and the pump. Recommend either installing a larger filter or a variable speed pump to adjust the flow to between 78 GPM for minimum turnover and 106 GPM for the maximum the filter can handle. Ensure signage is in place directing bathers to location of restroom entrance and doors to restrooms left unlocked when the office is closed. Facility planning to install keyfob entry on door that opens onto the pool deck from the restrooms. Will need an electrical permit for any electrical work done. Key fobs for gates and door need to be on a battery backup system or fail closed in the event of a power outage. Permit issued with the following conditions: No night swimming Pressure and vacuum gauges must remain in place with a TDH of between 63 and 82 ft head loss, or 78 GPM to 106 GPM for minimum turnover and restriction of the filter. TDH less than 53 or 119 GPM exceeds the main drains. Gate valve must remain locked in place. Paper permit will be on our website, https://eh.mecknc.gov/pools in 3-5 business days for your records.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Second step missing non-slip tread. .2521 Install ladders per manufacturer instructions. Ladder > 6” from pool wall. .2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms > 110 F. .2526(i) Water in restrooms shall not exceed 110 F.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Hose bib on pool deck missing a backflow preventer. .2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer.

View this inspection on the county portal ›

Apr 17, 2026 38 demerits · 11 violations
Inspector comments: Inspection conducted with CPO Jaxon Goldenberg-Sheetz and Johnny Hoffiz. TDH for pump is (6x1.13) + (16x2.31) =43.74 or 130 GPM per pump curve. Main drains only capable of handling 119 GPM. TR-140 filter only capable of handling 106 GPM. Will need to replace main drains with covers rated for at least 130 GPM and submit updated PDSC form. Facility planning to install keyfob entry on door that opens onto the pool deck from the restrooms. Will need an electrical permit for any electrical work done. Key fobs for gates and door need to be on a battery backup system or fail closed in the event of a power outage. Immediate suspension issued 6) 8) 12) 16) 24) 28) Contact Will Harrison (704) 507-6824 for re-inspection once issues have been corrected.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
A10RCFRxxx drain covers rated at 119 GPM. TDH calculation after a backwash is 130 GPM. Will need to change covers and submit updated PDSC form. .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. - Immediate suspension item.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
One weir missing styrofoam insert, not functioning. .2518(k) Provide functional weirs. - Immediate suspension item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Second step missing non-slip tread. .2521 Install ladders per manufacturer instructions. Ladder > 6” from pool wall. .2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Eyeball fitting assembly missing. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Immediate suspension item.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Throw rope 39 feet long. .2530(a) Provide US Coast Guard approved ring buoy with 33 foot throw rope. - Corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door from office not self-closing and self-latching. .2537(b) All gates and doors shall be self-closing, self-latching. - Immediate suspension item.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Vacuum cap damaged, can be opened without a tool. .2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. - Immediate suspension item.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Restrooms only accessible when the office is open. .2526(a) Provide at least one sink and toilet for residents and guests if furthest unit is more than 300 feet from the pool at hotels, motels, condominiums and apartments. - Facility working to install keyfob entry for door that opens on to pool deck from restroom hallway. Will need to be completed prior to permit being issued. - Immediate suspension item.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms > 110 F. .2526(i) Water in restrooms shall not exceed 110 F.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Hose bib on pool deck missing a backflow preventer. .2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer.

View this inspection on the county portal ›